NYCWY 4x120mm2 PVC 0.6/1kV Power Cable with Concentric Screen

Fixed installation for medium voltage (MV) power in both EX- and safe areas, general purposes. For installation in areas exposed to MUD and drilling/cleaning fluids. Meets the MUD resistance requirement in NEK TS 606:2009. Model: RFOU-8.7/15KV Brand: Grand Cable


keyword:Overhead/Aerial Cable

Detail


Application
The NYCWY cable range is used as fixed wiring power supply for indoor and outdoor applications with a voltage rating of 600/1000V where increased electrical conductivity with accompanying protection is required.

 

Applicable Standard

VDE 0276 Part 603 

IEC 60502 

BS EN/IEC 60332-1


Cable Construction

Conductor
RE: Class 1 solid copper conductor
RM: Class 2 stranded, round copper conductor
SM: Class 2 stranded, sectorial copper conductor

Insulation
PVC (Polyvinyl Chloride)

Bedding

PVC (Polyvinyl Chloride)

 

Concentric Conductor

Waveconal outer conductor - copper wire and counter spiral copper tape

Sheath
PVC (Polyvinyl Chloride)

 

Dimension Characteristics

NO. OF   CORES NOMINAL CROSS SECTIONAL   AREA
    mm²
CONDUCTOR TYPE NOMINAL OVERALL DIAMETER mm NOMINAL WEIGHT kg/km
2 10/10 RE 19.4 610
2 16/16 RE 20.4 840
2 25/25 RM 24.4 1299
3 10/20 RE 19.4 750
3 16/16 RE 21.4 1050
3 25/16 RM 25.5 1600
3 25/25 RM 25.5 1600
3 35/16 SM 25.7 1850
3 35/35 SM 27.6 1700
3 50/25 SM 28.7 2400
3 50/50 SM 28.7 2300
3 70/35 SM 33.8 3300
3 70/70 SM 32.8 2900
3 95/50 SM 37.8 4500
3 95/95 SM 37.8 400
3 120/70 SM 40.8 5000
3 120/120 SM 41.8 5500
3 150/70 SM 45 6000
3 150/150 SM 46 6750
3 185/95 SM 50 7500
3 185/185 SM 51 8500
3 240/120 SM 57 10000
4 10/10 RE 20.4 870
4 16/16 RE 23.4 1250
4 25/16 RM 27.6 1800
4 35/16 SM 28.6 2050
4 50/25 SM 32.8 2700
4 70/35 SM 36.8 3750
4 95/50 SM 43.9 5000
4 120/70 SM 47 6300
4 150/70 SM 51 7600
4 185/95 SM 56 9300
4 240/120 SM 63 11600

 

 